n6-01

(0570)

Online Tuning Selection

Sets the type of motor data that Online Tuning uses for OLV control.

0
Disabled
 
1
Line-to-Line Resistance Tuning

The drive adjusts the motor line-to-line resistance during run.

2
Voltage Correction Tuning

The drive adjusts the output voltage during run.

Note:

Setting 2 is enabled only when b8-01 = 0 [Energy Saving Control Selection = Disabled].

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n6-05

(05C7)

Expert

Online Tuning Gain

Sets the compensation gain when n6-01 = 2 [Online Tuning Selection = Voltage Correction Tuning]. Usually it is not necessary to change this parameter.

1.0

(0.1 - 50.0)

Details