Table 1. SSR1 Series Motor Code Setting for Specification of 200 V at 1750 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1202

1203

1205

1206

1208

120A

Voltage Class

V

200

200

200

200

200

200

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1750

1750

1750

1750

1750

1750

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

1.77

3.13

5.73

8.44

13.96

20.63

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

8.233

2.284

1.470

0.827

0.455

0.246

E5-06

PM d-axis Inductance (mH/phase)

mH

54.84

23.02

17.22

8.61

7.20

4.86

E5-07

PM q-axis Inductance (mH/phase)

mH

64.10

29.89

20.41

13.50

10.02

7.43

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

223.7

220.3

240.8

238.0

238.7

239.6

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-09

Minimum Output Frequency

Hz

4.4

4.4

4.4

4.4

4.4

4.4

L3-24

1

Motor Accel Time @ Rated Torque

s

0.092

0.076

0.051

0.066

0.075

0.083

n5-02

Motor Inertia Acceleration Time

s

0.092

0.076

0.051

0.066

0.075

0.083

n8-49

Heavy Load Id Current

%

-7.6

-11.5

-9.1

-19.0

-18.7

-23.4

 
Table 2. SSR1 Series Motor Code Setting for Specification of 200 V at 1750 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

120B

120D

120E

120F

1210

Voltage Class

V

200

200

200

200

200

Capacity

kW

7.5

11

15

18.5

22

Motor Rotation Speed

min-1

1750

1750

1750

1750

1750

E5-02

PM Motor Rated Power

kW

7.5

11.0

15.00

18.50

22.00

E5-03

PM Motor Rated Current (FLA)

A

28.13

41.4

55.4

68.2

80.6

E5-04

PM Motor Pole Count

-

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.198

0.094

0.066

0.051

0.037

E5-06

PM d-axis Inductance (mH/phase)

mH

4.15

3.40

2.45

2.18

1.71

E5-07

PM q-axis Inductance (mH/phase)

mH

5.91

3.91

3.11

2.55

2.05

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

258.2

239.3

248.1

253.6

250.0

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

87.5

87.5

87.5

87.5

87.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

87.5

87.5

87.5

87.5

87.5

E1-09

Minimum Output Frequency

Hz

4.4

4.4

4.4

4.4

4.4

L3-24

1

Motor Accel Time @ Rated Torque

s

0.077

0.084

0.102

0.101

0.098

n5-02

Motor Inertia Acceleration Time

s

0.077

0.084

0.102

0.101

0.098

n8-49

Heavy Load Id Current

%

-18.5

-10.9

-16.5

-11.3

-12.8

Table 3. SSR1 Series Motor Code Setting for Specification of 400 V at 1750 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1232

1233

1235

1236

1238

123A

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1750

1750

1750

1750

1750

1750

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

0.89

1.56

2.81

4.27

7.08

10.31

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

25.370

9.136

6.010

3.297

1.798

0.982

E5-06

PM d-axis Inductance (mH/phase)

mH

169.00

92.08

67.71

34.40

32.93

22.7

E5-07

PM q-axis Inductance (mH/phase)

mH

197.50

119.56

81.71

54.00

37.70

26.80

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

392.6

440.6

478.3

466.3

478.8

478.1

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-09

Minimum Output Frequency

Hz

4.4

4.4

4.4

4.4

4.4

4.4

L3-24

1

Motor Accel Time @ Rated Torque

s

0.092

0.076

0.051

0.066

0.075

0.083

n5-02

Motor Inertia Acceleration Time

s

0.092

0.076

0.051

0.066

0.075

0.083

n8-49

Heavy Load Id Current

%

-8.6

-11.5

-10.3

-19.8

-8.5

-11.0

Table 4. SSR1 Series Motor Code Setting for Specification of 400 V at 1750 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

123B

123D

123E

123F

1240

1242

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

7.5

11

15

18.5

22

30

Motor Rotation Speed

min-1

1750

1750

1750

1750

1750

1750

E5-02

PM Motor Rated Power

kW

7.5

11.0

15

18.50

22.00

30.00

E5-03

PM Motor Rated Current (FLA)

A

13.65

20.7

27.5

33.4

39.8

52.0

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.786

0.349

0.272

0.207

0.148

0.235

E5-06

PM d-axis Inductance (mH/phase)

mH

16.49

13.17

10.30

8.72

6.81

5.4

E5-07

PM q-axis Inductance (mH/phase)

mH

23.46

15.60

12.77

11.22

8.47

7.26

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

520.0

481.5

498.8

509.5

503.9

561.7

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

87.5

87.5

87.5

87.5

87.5

87.5

E1-09

Minimum Output Frequency

Hz

4.4

4.4

4.4

4.4

4.4

4.4

L3-24

1

Motor Accel Time @ Rated Torque

s

0.077

0.084

0.102

0.101

0.098

0.130

n5-02

Motor Inertia Acceleration Time

s

0.077

0.084

0.102

0.101

0.098

0.130

n8-49

Heavy Load Id Current

%

-18.6

-12.5

-15.5

-17.9

-15.1

-16.8

Table 5. SSR1 Series Motor Code Setting for Specification of 200 V at 1450 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1302

1303

1305

1306

1308

130A

Voltage Class

V

200

200

200

200

200

200

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1450

1450

1450

1450

1450

1450

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

1.88

3.13

5.63

8.33

14.17

20.63

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

3.190

1.940

1.206

0.665

0.341

0.252

E5-06

PM d-axis Inductance (mH/phase)

mH

32.15

26.12

14.72

12.27

8.27

6.49

E5-07

PM q-axis Inductance (mH/phase)

mH

41.74

34.30

20.15

14.77

9.81

7.74

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

264.3

269.6

284.3

287.1

284.5

298.0

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-09

Minimum Output Frequency

Hz

3.6

3.6

3.6

3.6

3.6

3.6

L3-24

1

Motor Accel Time @ Rated Torque

s

0.098

0.071

0.066

0.087

0.085

0.072

n5-02

Motor Inertia Acceleration Time

s

0.098

0.071

0.066

0.087

0.085

0.072

n8-49

Heavy Load Id Current

%

-6.6

-10.9

-13.5

-9.0

-9.5

-10.1

Table 6. SSR1 Series Motor Code Setting for Specification of 200 V at 1450 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

130B

130D

130E

130F

1310

Voltage Class

V

200

200

200

200

200

Capacity

kW

7.5

11

15

18.5

22

Motor Rotation Speed

min-1

1450

1450

1450

1450

1450

E5-02

PM Motor Rated Power

kW

7.5

11.0

15.00

18.50

22.00

E5-03

PM Motor Rated Current (FLA)

A

27.71

39.6

55.5

65.6

75.1

E5-04

PM Motor Pole Count

-

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.184

0.099

0.075

0.057

0.041

E5-06

PM d-axis Inductance (mH/phase)

mH

6.91

4.07

3.29

2.53

1.98

E5-07

PM q-axis Inductance (mH/phase)

mH

7.66

4.65

3.84

3.01

2.60

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

335.0

303.9

311.2

300.9

327.7

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

72.5

72.5

72.5

72.5

72.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

72.5

72.5

72.5

72.5

72.5

E1-09

Minimum Output Frequency

Hz

3.6

3.6

3.6

3.6

3.6

L3-24

1

Motor Accel Time @ Rated Torque

s

0.084

0.096

0.085

0.080

0.122

n5-02

Motor Inertia Acceleration Time

s

0.084

0.096

0.085

0.080

0.122

n8-49

Heavy Load Id Current

%

-6.0

-9.3

-10.7

-13.2

-15.7

Table 7. SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1332

1333

1335

1336

1338

133A

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1450

1450

1450

1450

1450

1450

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

0.94

1.56

2.81

4.27

6.98

10.21

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

12.760

7.421

4.825

2.656

1.353

0.999

E5-06

PM d-axis Inductance (mH/phase)

mH

128.60

85.11

58.87

46.42

31.73

26.20

E5-07

PM q-axis Inductance (mH/phase)

mH

166.96

113.19

80.59

60.32

40.45

30.94

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

528.6

544.2

568.5

572.8

562.9

587.6

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-09

Minimum Output Frequency

Hz

3.6

3.6

3.6

3.6

3.6

3.6

L3-24

1

Motor Accel Time @ Rated Torque

s

0.098

0.071

0.066

0.087

0.085

0.072

n5-02

Motor Inertia Acceleration Time

s

0.098

0.071

0.066

0.087

0.085

0.072

n8-49

Heavy Load Id Current

%

-6.6

-9.2

-13.5

-12.1

-13.7

-10.1

Table 8. SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

133B

133D

133E

133F

1340

1342

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

7.5

11

15

18.5

22

30

Motor Rotation Speed

min-1

1450

1450

1450

1450

1450

1450

E5-02

PM Motor Rated Power

kW

7.5

11.0

15

18.50

22.00

30.00

E5-03

PM Motor Rated Current (FLA)

A

13.85

19.5

27.4

32.9

37.6

52.5

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.713

0.393

0.295

0.223

0.164

0.137

E5-06

PM d-axis Inductance (mH/phase)

mH

27.06

15.51

12.65

9.87

7.90

7.01

E5-07

PM q-axis Inductance (mH/phase)

mH

33.45

19.63

15.87

12.40

10.38

8.68

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

670.1

612.7

624.6

610.4

655.4

708.4

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

72.5

72.5

72.5

72.5

72.5

72.5

E1-09

Minimum Output Frequency

Hz

3.6

3.6

3.6

3.6

3.6

3.6

L3-24

1

Motor Accel Time @ Rated Torque

s

0.084

0.096

0.085

0.080

0.122

0.108

n5-02

Motor Inertia Acceleration Time

s

0.084

0.096

0.085

0.080

0.122

0.108

n8-49

Heavy Load Id Current

%

-12.2

-15.5

-15.1

-16.0

-15.7

-11.5

Table 9. SSR1 Series Motor Code Setting for Specification of 200 V at 1150 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1402

1403

1405

1406

1408

140A

Voltage Class

V

200

200

200

200

200

200

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1150

1150

1150

1150

1150

1150

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

1.88

3.02

6.00

8.85

14.27

20.21

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

4.832

2.704

1.114

0.511

0.412

0.303

E5-06

PM d-axis Inductance (mH/phase)

mH

48.68

32.31

19.22

12.15

7.94

11.13

E5-07

PM q-axis Inductance (mH/phase)

mH

63.21

40.24

24.38

15.35

11.86

14.06

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

320.4

327.1

364.4

344.4

357.5

430.8

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-09

Minimum Output Frequency

Hz

2.9

2.9

2.9

2.9

2.9

2.9

L3-24

1

Motor Accel Time @ Rated Torque

s

0.062

0.044

0.080

0.090

0.067

0.072

n5-02

Motor Inertia Acceleration Time

s

0.062

0.044

0.080

0.090

0.067

0.072

n8-49

Heavy Load Id Current

%

-8.8

-9.9

-9.3

-10.0

-17.7

-12.3

Table 10. SSR1 Series Motor Code Setting for Specification of 200 V at 1150 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

140B

140D

140E

140F

1410

Voltage Class

V

200

200

200

200

200

Capacity

kW

7.5

11

15

18.5

22

Motor Rotation Speed

min-1

1150

1150

1150

1150

1150

E5-02

PM Motor Rated Power

kW

7.5

11.0

15

18.50

22.00

E5-03

PM Motor Rated Current (FLA)

A

26.67

39.9

55.6

63.5

74.4

E5-04

PM Motor Pole Count

-

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.165

0.113

0.084

0.066

0.048

E5-06

PM d-axis Inductance (mH/phase)

mH

6.59

4.96

3.83

3.33

2.38

E5-07

PM q-axis Inductance (mH/phase)

mH

8.55

6.12

4.65

4.50

3.15

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

391.5

384.4

372.1

421.3

410.9

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

57.5

57.5

57.5

57.5

57.5

E1-05

Maximum Output Voltage

V

190.0

190.0

190.0

190.0

190.0

E1-06

Base Frequency

Hz

57.5

57.5

57.5

57.5

57.5

E1-09

Minimum Output Frequency

Hz

2.9

2.9

2.9

2.9

2.9

L3-24

1

Motor Accel Time @ Rated Torque

s

0.088

0.073

0.062

0.091

0.092

n5-02

Motor Inertia Acceleration Time

s

0.088

0.073

0.062

0.091

0.092

n8-49

Heavy Load Id Current

%

-15.3

-13.9

-14.4

-17.9

-15.9

Table 11. SSR1 Series Motor Code Setting for Specification of 400 V at 1150 min-1 (r/min)

No.

Name

Unit

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

1432

1433

1435

1436

1438

143A

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

0.4

0.75

1.5

2.2

3.7

5.5

Motor Rotation Speed

min-1

1150

1150

1150

1150

1150

1150

E5-02

PM Motor Rated Power

kW

0.4

0.75

1.5

2.2

3.7

5.5

E5-03

PM Motor Rated Current (FLA)

A

0.94

1.51

3.00

4.43

7.08

10.10

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

19.320

10.800

4.456

2.044

1.483

1.215

E5-06

PM d-axis Inductance (mH/phase)

mH

194.70

129.20

76.88

48.60

37.58

44.54

E5-07

PM q-axis Inductance (mH/phase)

mH

252.84

160.90

97.52

61.40

47.65

56.26

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

640.9

654.1

728.8

688.9

702.0

861.5

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-09

Minimum Output Frequency

Hz

2.9

2.9

2.9

2.9

2.9

2.9

L3-24

1

Motor Accel Time @ Rated Torque

s

0.062

0.044

0.080

0.090

0.067

0.072

n5-02

Motor Inertia Acceleration Time

s

0.062

0.044

0.080

0.090

0.067

0.072

n8-49

Heavy Load Id Current

%

-8.8

-9.9

-9.3

-10.0

-12.8

-12.3

Table 12. SSR1 Series Motor Code Setting for Specification of 400 V at 1150 min-1 (r/min)

No.

Name

Unit

   

Motor Code (setting value of E5-01)

E5-01

PM Motor Code Selection

-

143B

143D

143E

143F

1440

1442

Voltage Class

V

400

400

400

400

400

400

Capacity

kW

7.5

11

15

18.5

22

30

Motor Rotation Speed

min-1

1150

1150

1150

1150

1150

1150

E5-02

PM Motor Rated Power

kW

7.5

11.0

15

18.50

22.00

30.00

E5-03

PM Motor Rated Current (FLA)

A

13.33

19.9

27.8

31.8

37.2

52.1

E5-04

PM Motor Pole Count

-

6

6

6

6

6

6

E5-05

PM Motor Resistance (ohms/phase)

Ω

0.660

0.443

0.331

0.264

0.192

0.140

E5-06

PM d-axis Inductance (mH/phase)

mH

26.36

19.10

15.09

13.32

9.52

8.16

E5-07

PM q-axis Inductance (mH/phase)

mH

34.20

24.67

18.56

18.00

12.60

11.40

E5-09

PM Back-EMF Vpeak (mV/(rad/s))

mVs/rad

783.0

762.2

749.6

842.7

821.8

872.3

E5-24

PM Back-EMF L-L Vrms (mV/rpm)

mV/min-1

0.0

0.0

0.0

0.0

0.0

0.0

E1-04

Maximum Output Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-05

Maximum Output Voltage

V

380.0

380.0

380.0

380.0

380.0

380.0

E1-06

Base Frequency

Hz

57.5

57.5

57.5

57.5

57.5

57.5

E1-09

Minimum Output Frequency

Hz

2.9

2.9

2.9

2.9

2.9

2.9

L3-24

1

Motor Accel Time @ Rated Torque

s

0.088

0.073

0.062

0.091

0.092

0.125

n5-02

Motor Inertia Acceleration Time

s

0.088

0.073

0.062

0.091

0.092

0.125

n8-49

Heavy Load Id Current

%

-15.3

-16.7

-14.9

-17.9

-15.9

-17.7

1