YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H2-01
(040B)
Term MA/MB-MC Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
E
(0 - 1FF)
Details
H2-02
(040C)
Term P1-C1 Function Selection
Sets the function for MFDO terminal P1-C1.
0
H2-03
(040D)
Term P2-C2 Function Selection
Sets the function for MFDO terminal P2-C2.
2
H2-06
(0437)
Watt Hour Output Unit Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt Hour Pulse Output].
(0 - 4)
H2-07
(0B3A)
Modbus Register 1 Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2 Address Select
H2-10
(0B3D)
Modbus Register 2 Bit Select
H2-20
(1540)
Comparator 1 Monitor Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
102
(000 - 999)
H2-21
(1541)
Comparator 1 Lower Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
H2-22
(1542)
Comparator 1 Upper Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection].
(0.0 - 10.0%)
H2-24
(1544)
Comparator 1 On-Delay Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
H2-25
(1545)
Comparator 1 Off-Delay Time
Sets the off-delay time for comparator 1.
H2-26
(1546)
Comparator 2 Monitor Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-26 = 103 to monitor U1-03 [Output Current].
103
H2-27
(1547)
Comparator 2 Lower Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
H2-30
(154A)
Comparator 2 On-Delay Time
Sets the on-delay time for comparator 2.
H2-31
(154B)
Comparator 2 Off-Delay Time
Sets the off-delay time for comparator 2.
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the monitor selected with H2-20 [Comparator 1 Monitor Selection].
0.0s
(0.0 - 10.0 s)
H2-33
(159B)
Comparator1 Protection Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
4
H2-34
(159C)
Comparator 2 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the monitor selected with H2-26 [Comparator 2 Monitor Selection].
H2-35
(159D)
Comparator2 Protection Selection
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
H2-36
(159E)
Comparator 1 Ineffective Time
Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled.
(0.0 - 1000.0 s)
H2-37
(159F)
Comparator 2 Ineffective Time
Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled.
H2-40
(0B58)
Mbus Reg 15E0h bit0 Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
H2-41
(0B59)
Mbus Reg 15E0h bit1 Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
H2-42
(0B5A)
Mbus Reg 15E0h bit2 Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
H2-60
(1B46)
Expert
Term MA,MB,MC Secondary Function
Sets the second function for terminal MA/MB-MC. Outputs the logical calculation results of the terminals set to functions by H2-01 [Term MA,MB,MC Function Selection].
(0 - FF)
H2-61
(1B47)
Term MA,MB,MC Logical Operation
Sets the logical operation for the functions set in H2-01 [Term MA,MB,MC Function Selection] and H2-60 [Term MA,MB,MC Secondary Function].
(0 - 8)
H2-62
(1B48)
Term MA,MB,MC Minimum ON Time
Sets the minimum ON time that the drive uses to output the logical calculation results from terminal MA/MB-MC.
0.1 s
(0.0 - 25.0 s)
H2-63
(1B49)
Terminal P1 Secondary Function
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the terminals set to functions by H2-02 [Term P1 Function Selection].
H2-64
(1B4A)
Terminal P1 Logical Operation
Sets the logical operation for the functions set in H2-02 [Term P1 Function Selection] and H2-63 [Terminal P1 Secondary Function].
H2-65
(1B4B)
Terminal P1 Minimum ON Time
Sets the minimum ON time used to output the logical calculation results from terminal P1-C1.
H2-66
(1B4C)
Terminal P2 Secondary Function
Sets the second function for terminal P2-C2. Outputs the logical calculation results of the terminals assigned to functions by H2-03 [Term P2 Function Selection].
H2-67
(1B4D)
Terminal P2 Logical Operation
Sets the logical operation for the functions set in H2-03 [Term P2 Function Selection] and H2-66 [Terminal P2 Secondary Function].
H2-68
(1B4E)
Terminal P2 Minimum ON Time
Sets the minimum ON time used to output the logical calculation results from terminal P2-C2.