YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set some parameters to their correct settings.
FFFF
(0000 - FFFF)
Details
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units from o1-58 [Motor Power Unit Selection].
Determined by o2-04, C6-01
(0.10 - 30.00 kW)
E5-03
(032B)
Motor Rated Current (FLA)
Sets the PM motor rated current (FLA).
(10% to 200% of the drive rated current)
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
4
(2 - 120)
E5-05
(032D)
PM Motor Resistance (ohms/phase)
Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.
0.100 Ω
(0.000 - 65.000 Ω)
E5-06
(032E)
PM d-axis Inductance (mH/phase)
Sets the PM motor d-axis inductance.
1.00 mH
(0.00 - 300.00 mH)
E5-07
(032F)
PM q-axis Inductance (mH/phase)
Sets the PM motor q-axis inductance.
(0.00 - 600.00 mH)
E5-09
(0331)
PM Back-EMF Vpeak (mV/(rad/s))
Sets the peak value of PM motor induced voltage.
0.0 mV/(rad/sec)
(0.0 - 2000.0 mV/(rad/s))
E5-24
(0353)
PM Back-EMF L-L Vrms (mV/rpm)
Sets the RMS value for PM motor line voltage.
200 V Class:
100.0 mV/min-1
400 V Class:
200.0 mV/min-1
(0.0 - 6500.0 mV/min-1)
E5-25
(035E)
Expert
Polarity Estimation Timeout
Sets the function that switches polarity for initial polarity estimation. Usually it is not necessary to change this setting.
0
(0, 1)