E3-01
(0319)
Motor 2 Control Mode Selection
Sets the control method for motor 2.
When you change this setting, the drive will set all parameters that are dependent on this parameter to their default settings.
0
(0, 2)
Details
E3-04
(031A)
Motor 2 Maximum Output Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
E3-05
(031B)
Motor 2 Maximum Output Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
(200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V)
E3-06
(031C)
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
(0.0 - E3-04)
E3-07
(031D)
Motor 2 Mid Point A Frequency
Sets a middle output frequency for the motor 2 V/f pattern.
E3-08
(031E)
Motor 2 Mid Point A Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
E3-09
(031F)
Motor 2 Minimum Output Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
E3-10
(0320)
Motor 2 Minimum Output Voltage
Sets the minimum output voltage for the motor 2 V/f pattern.
E3-11
(0345)
Expert
Motor 2 Mid Point B Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 Hz
E3-12
(0346)
Motor 2 Mid Point B Voltage
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(200 V Class: 0.0 to 255.0 V, 400 V Class: 0.0 to 510.0 V)
E3-13
(0347)
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the constant output range. Usually it is not necessary to change this parameter.