Parameters that Change from the Default Settings with E3-01 [Motor 2 Control Mode Selection]

The values for the parameters in these tables depend on the values for parameter E3-01. When you change the setting for E3-01, the default settings will change.

 

No.

Name

Range

Unit

Motor 2 Control Method (setting value of E3-01)

V/f

(0)

OLV

(2)

C3-21

Motor 2 Slip Compensation Gain

0.0 - 2.50

0.1

0.0

1.0

C3-22

Motor 2 Slip Comp Delay Time

0 - 10000

1 ms

2000

200

E3-04

Motor 2 Maximum Output Frequency

40.0 - 590.0

0.1 Hz

60.0

60.0

E3-05

Motor 2 Maximum Output Voltage

0.0 - 255.0

1

0.1 V

200.0

200.0

E3-06

Motor 2 Base Frequency

0.0 - 590.0

0.1 Hz

60.0

60.0

E3-07

Motor 2 Mid Point A Frequency

0.0 - 590.0

0.1 Hz

3.0

3.0

E3-08

Motor 2 Mid Point A Voltage

0.0 - 255.0

1

0.1 V

15.0

11.0

E3-09

Motor 2 Minimum Output Frequency

0.0 - 590.0

0.1 Hz

1.5

0.5

E3-10

Motor 2 Minimum Output Voltage

0.0 - 255.0

1

0.1 V

9.0

2.0

E3-11

Motor 2 Mid Point B Frequency

0.0 - 590.0

Determined by o1-04

0.0

0.0

E3-12

Motor 2 Mid Point B Voltage

0.0 - 255.0

1

0.1 V

0.0

0.0

E3-13

Motor 2 Base Voltage

0.0 - 255.0

1

0.1 V

0.0

0.0

 
1