Parameters Changed by E1-03 [V/f Pattern Selection]

The values for parameters A1-02 [Control Method Selection] and E1-03 [V/f Pattern Selection] change the default settings for the parameters in these tables:

Table 1. Parameters Changed by E1-03 (B001 - B018, 2001 - 2021, and 4001 - 4012)

No.

Unit

Setting Value

Control Method (A1-02 Setting)

E1-03

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

1

OLV

(2)

OLV/PM

(5)

AOLV/PM

(6)

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

60.0

2

2

E1-05

3

V

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

2

2

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

60.0

2

2

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

3.0

-

-

E1-08

3

V

16.0

16.0

16.0

16.0

35.0

50.0

35.0

50.0

19.0

24.0

19.0

24.0

16.0

16.0

16.0

16.0

12.0

-

-

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

0.5

2

2

E1-10

3

V

12.0

12.0

12.0

12.0

8.0

9.0

8.0

9.0

12.0

13.0

12.0

15.0

12.0

12.0

12.0

12.0

2.5

-

-

 
Table 2. Parameters Changed by E1-03 (2030 - 2082 and 4018 - 4060)

No.

Unit

Setting Value

Control Method (A1-02 Setting)

E1-03

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

1

OLV

(2)

OLV/PM

(5)

AOLV/PM

(6)

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

60.0

2

2

E1-05

3

V

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

200.0

2

2

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

60.0

2

2

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

3.0

-

-

E1-08

3

V

14.0

14.0

14.0

14.0

35.0

50.0

35.0

50.0

18.0

23.0

18.0

23.0

14.0

14.0

14.0

14.0

11.0

-

-

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

0.5

2

2

E1-10

3

V

7.0

7.0

7.0

7.0

6.0

7.0

6.0

7.0

9.0

11.0

9.0

13.0

7.0

7.0

7.0

7.0

2.0

-

-

1

These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].

2

The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].

3

This is the value for 200 V class drives. Double the value for 400 V class drives.