C4: Torque Compensation

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-01

(0215)

RUN

Torque Compensation Gain

Sets the gain for the torque compensation function. Use this parameter value for motor 1 when operating multiple motors.

Note:

When A1-02 = 8 [Control Method Selection = EZOLV], you cannot change this parameter during drive run.

Determined by A1-02

(0.00 - 2.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-02

(0216)

RUN

Torque Compensation Delay Time

Sets the torque compensation delay time. Usually it is not necessary to change this setting.

Note:

When A1-02 = 5, 8 [Control Method Selection = OLV/PM,EZOLV], you cannot change the setting while the drive is running.

Determined by A1-02

(0 - 60000 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-03

(0217)

Torque Compensation @ FWD Start

Set the amount of torque reference for forward start as a percentage of the motor rated torque.

0.0%

(0.0 - 200.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-04

(0218)

Torque Compensation @ REV Start

Sets the amount of torque reference for reverse start as a percentage of the motor rated torque.

0.0%

(-200.0 - 0.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-05

(0219)

Torque Compensation Time

Sets the starting torque constant to use with C4-03 and C4-04 [Torque Compensation @ FWD/REV Start].

10 ms

(0 - 200 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-06

(021A)

Motor 2 Torque Comp Delay Time

Sets the value if ov [Overvoltage] occurs with sudden changes in the load, at the end of acceleration, or at the start of deceleration.

150 ms

(0 - 10000 ms)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-07

(0341)

RUN

Motor 2 Torque Compensation Gain

Sets the gain for motor 2 torque compensation function when using the Motor Switch function.

1.00

(0.00 - 2.50)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

C4-23

(1583)

Expert

Current Control Gain

Sets the Current control gain. Usually it is not necessary to change this parameter.

1.00

(0.50 - 2.50)

Details