Jump to main content

E9: Motor Setting

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-01

(11E4)

Motor Type Selection

Sets the type of motor.

0
Induction (IM)
 
1
Permanent Magnet (PM)
 
2
Synchronous Reluctance (SynRM)
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-02

(11E5)

Maximum Speed

Sets the maximum speed of the motor.

Determined by E9-01

(40.0 - 120.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-03

(11E6)

Rated Speed

Sets the rated rotation speed of the motor.

Determined by E9-01

(100 - 7200 min-1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-04

(11E7)

Base Frequency

Sets the rated frequency of the motor.

Determined by E9-01

(40.0 - 120.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-05

(11E8)

Motor Rated Voltage

Sets the rated voltage of the motor.

200 V Class: 200.0 V,

400 V Class: 400.0 V

(200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-06

(11E9)

Motor Rated Current (FLA)

Sets the motor rated current in amps.

Determined by E9-01 and o2-04

(10% to 200% of the drive rated current)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-07

(11EA)

Motor Rated Power

Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].

Determined by E9-02 and o2-04

(0.00 - 650.00 kW)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-08

(11EB)

Motor Pole Count

Sets the number of motor poles.

4

(2 to 120)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-09

(11EC)

Motor Rated Slip

Sets the motor rated slip.

0.000 Hz

(0.000 - 20.000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-10

(11ED)

Motor Line-to-Line Resistance

Sets the line-to-line resistance for the motor stator windings.

Determined by o2-04

(0.000 - 65.000 Ω)

Details