No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-01

(042C)

Terminal RP Pulse Train Function

Sets the function for pulse train input terminal RP.

0
Frequency Reference

When b1-01 = 4 [Frequency Reference Selection 1 = Pulse Train Input] or b1-15 = 4 [Frequency Reference Selection 2 = Pulse Train Input], the drive inputs the frequency reference received from terminal RP.

1
PID Feedback Value

The drive inputs the PID control feedback value received from terminal RP.

2
PID Setpoint Value

The drive inputs the PID control target value received from terminal RP.

3
Speed Feedback (V/F Control)

Select V/f Control method to enable simple encoder feedback.

0

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-02

(042D)

RUN

Terminal RP Frequency Scaling

Sets the frequency of the pulse train input signal used when the item selected with H6-01 [Terminal RP Pulse Train Function] is input at 100%.

1440 Hz

(100 - 32000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-03

(042E)

RUN

Terminal RP Function Gain

Sets the gain used when the function in H6-01 [Terminal RP Pulse Train Function] is input to terminal RP.

100.0%

(0.0 - 1000.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-04

(042F)

RUN

Terminal RP Function Bias

Sets the bias used when the function in H6-01 [Terminal RP Pulse Train Function] is input to terminal RP. Sets a value at the time when the pulse train is 0 Hz.

0.0%

(-100.0 - 100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-05

(0430)

RUN

Terminal RP Filter Time

Sets the time constant for the pulse train input primary delay filters.

0.10 s

(0.00 - 2.00 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-06

(0431)

RUN

Terminal MP Monitor Selection

Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx monitor.

102

(000, 031, 101, 102, 105, 116, 501, 502, 801 - 809, 821 - 825, 831 - 839, 851 - 855)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-07

(0432)

RUN

Terminal MP Frequency Scaling

Sets the frequency of the pulse train output signal used when the monitor set with H6-06 [Terminal MP Monitor Selection] is 100%.

1440 Hz

(0 - 32000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H6-08

(043F)

Terminal RP Minimum Frequency

Sets the minimum frequency of the pulse train signal that terminal RP can detect.

0.5 Hz

(0.1 - 1000.0 Hz)

Details