YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive rated current)
Details
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
(0.000 - 20.000 Hz)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load voltage.
(0 to E2-01)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
When A1-02 = 0 [Control Method Selection = V/f], the maximum value is 120.
When A1-02 = 2 [OLV], the maximum value is 48.
4
(2 - 120)
E2-05
(0312)
Motor Line-to-Line Resistance
Sets the line-to-line resistance for the motor stator windings.
(0.000 - 65.000 Ω)
E2-06
(0313)
Motor Leakage Inductance
Sets the voltage drop from motor leakage inductance when the motor is operating at the rated frequency and rated current. This value is a percentage of Motor Rated Voltage.
(0.0 - 60.0%)
E2-07
(0314)
Motor Saturation Coefficient 1
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
0.50
(0.00 - 0.50)
E2-08
(0315)
Motor Saturation Coefficient 2
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
0.75
(E2-07 - 0.75)
E2-09
(0316)
Expert
Motor Mechanical Loss
Sets the mechanical loss of the motor. It is set as a percentage of E2-11 [Motor Rated Power]. Usually it is not necessary to change this setting.
0.0%
(0.0 - 10.0%)
E2-10
(0317)
Motor Iron Loss
Sets the motor iron loss.
(0 - 65535 W)
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
(0.00 - 650.00)