Jump to main content

n7: EZ Drive

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-01

(3111)

Expert

Damping Gain for Low Frequency

Sets the oscillation suppression gain for the low speed range.

1.0

(0.1 - 10.0)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-05

(3115)

Expert

Response Gain for Load Changes

Sets the response gain related to changes in the load.

50

(10 - 1000)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-07

(3117)

Expert

Speed Calculation Gain1

Sets the speed calculation gain during usual operation. Usually it is not necessary to change this setting.

15.0

(1.0 - 50.0)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-08

(3118)

Expert

Speed Calculation Gain2

Sets the speed calculation gain during a speed search.

25.0

(1.0 - 50.0)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-10

(311A)

Expert

Pull-in Current Switching Speed

Sets the speed range to operate with the pull-in current command. Drive rated frequency = 100% value. If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.

10.0%

(0.0 - 100.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-17

(3122)

Resistance TemperatureCorrection

Sets the function to adjust for changes in the motor resistance value caused by changes in the temperature.

0
Invalid
 
1
Valid (Only 1 time)
 
2
Valid (Every time)
 

1

(0 to 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

n7-19

(3128)

Expert

Flux Error Compensation Gain

Sets the gain for magnetic flux compensation. Usually it is not necessary to change this setting.

5000%

(0 - 50000%)

Details