CF
|
Control Fault
|
Motor parameters are set incorrectly
|
Correctly set the motor parameters and do Auto-Tuning again.
|
|
The torque limit setting is too low.
|
Adjust L7-01 to L7-04 [Torque Limit].
|
|
The load inertia is too large.
|
-
Adjust C1-02, C1-04, C1-06, and C1-08 [Deceleration Times].
-
Set the frequency reference to the minimum output frequency, and stop the Run command when the drive stops deceleration.
|
|
The drive is trying to ramp to stop a machine that cannot do ramp to stop or on a machine for which deceleration is not necessary.
|
Correctly set b1-03 [Stopping Method Selection].
|
|
The motor and drive are connected incorrectly.
|
Correct wiring errors.
|
|
Line-to-line Resistance Tuning is not done.
|
Do Stationary Auto-Tuning for Line-to-Line Resistance.
|
|
The drive received a Run command while the motor was coasting.
|
|
|
|