The drive is operating the motor (the drive is in Drive Mode).
|
Stop the drive and change to Programming Mode.
|
|
Parameter A1-01 = 0 [Access Level Selection = Operation Only].
|
Set A1-01 = 2 [Access Level Selection = Advanced Level] or A1-01 = 3 [Expert Level].
|
|
Parameter H1-xx = 1B [MFDI Function Select = Programming Lockout].
|
Activate the terminals to which H1-xx = 1B is set, and then change the parameters.
|
|
You entered an incorrect password in A1-04 [Password].
|
-
Enter the correct password to A1-04 again.
-
If you forgot the password, set the password again with A1-04 and A1-05 [Password Setting].
Note:
If you set the password, you cannot change these parameters until the password aligns:
-
A1-01 [Access Level Selection]
-
A1-02 [Control Method Selection]
-
A1-03 [Initialize Parameters]
-
A1-06 [Application Preset]
-
A1-07 [DriveWorksEZ Function Selection]
-
A2-01 to A2-32 [User Parameter 1 to User Parameter 32]
|
|
The drive detected Uv [Undervoltage].
|
|