Code

Name

Causes

Possible Solutions

oPE05

Run Cmd/Freq Ref Source Sel Err

The setting to assign the Run command or frequency reference to an option card or the pulse train input is incorrect.

Correct the parameter settings.

b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] is set, but there is no option card connected to the drive.

Connect an option card to the drive.

b1-02 = 3 [Run Command Selection 1 = Option PCB] is set, but there is no option card connected to the drive.

These parameters are set at the same time:

  • b1-01 = 4 [Pulse Train Input]

  • H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠ Frequency Reference]

Set H6-01 = 0.