Code

Name

Causes

Possible Solutions

oPE03

Multi-Function Input Setting Err

The settings for these parameters do not agree:

  • H1-01 to H1-07 [Terminals S1 to S8 Function Selection]

  • H7-01 to H7-04 [Virtual Multi-Function Inputs 1 to 4]

Correct the parameter settings.

The settings for MFDIs overlap.

Note:

This does not include H1-xx = 20 to 2F [MFDI Function Select = External Fault] and [Reserved].

Set the parameters correctly to prevent MFDI function overlap.

You did not set these pairs of MFDI functions to Digital Inputs (H1-xx and H7-01 to H7-04) at the same time:

  • Setting values 10 [Up Command] and 11 [Down Command]

  • Setting values 75 [Up 2 Command] and 76 [Down 2 Command]

  • Setting values 42 [Run Command (2-Wire Sequence 2)] and 43 [FWD/REV (2-Wire Sequence 2)]

Set the MFDI pairs.

You set a minimum of two of these MFDI combinations to Digital Inputs (H1-xx and H7-01 to H7-04) at the same time:

  • Setting values 10 [Up Command] and 11 [Down Command]

  • Setting values 75 [Up 2 Command] and 76 [Down 2 Command]

  • Setting value A [Accel/Decel Ramp Hold]

  • Setting value 1E [Reference Sample Hold]

  • Setting values 44 to 46 [Add Offset Frequency 1 to 3 (d7-01 to d7-03)]

Remove the function settings that are not in use.

You set these commands in Digital Inputs (H1-xx and H7-01 to H7-04) at the same time:

  • Setting values 61 [Speed Search from Fmax] and 62 [Speed Search from Fref]

  • Setting values 65, 66, 7A, 7B [KEB Ride-Thru 1 or 2 Activate] and 68 [High Slip Braking (HSB) Activate]

  • Setting values 16 [Motor 2 Selection] and 1A [Accel/Decel Time Selection 2]

  • Setting values 65, 66 [KEB Ride-Thru 1 Activate] and 7A, 7B [KEB Ride-Thru 2 Activate]

  • Setting values 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-Wire)] and 42, 43 [Run Command (2-Wire Sequence 2), FWD/REV (2-Wire Sequence 2)]

  • Setting values 60 [DC Injection Braking Command] and 6A [Drive Enable]

  • Setting values 16 [Motor 2 Selection] and 75, 76 [Up 2 Command, Down 2 Command]

Remove the function settings that are not in use.

Settings for N.C. and N.O. input [H1-xx] for these functions were selected at the same time:

  • Setting value 15 [Fast Stop (N.O.)]

  • Setting value 17 [Fast Stop (N.C.)]

Remove one of the function settings.

You entered these settings while H1-xx = 2 [External Reference 1/2 Selection]:

  • b1-15 = 4 [Frequency Reference Selection 2 = Pulse Train Input]

  • H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠ Frequency Reference]

Set H6-01 = 0.

You entered these settings while H1-xx = 2 [External Reference 1/2 Selection]:

  • b1-15 = 3 [Option PCB] or b1-16 = 3 [Run Command Selection 2 = Option PCB]

  • You did not connect an option to the drive.

Connect an input option to the drive.

You entered these settings while H1-xx = 2 [External Reference 1/2 Selection]:

  • b1-15 = 1 [Analog Input]

  • H3-02 ≠ 0 [Terminal A1 Function Selection ≠ Frequency Reference] or H3-10 ≠ 0 [Terminal A2 Function Selection ≠ Frequency Reference]

Set H3-02 = 0 or H3-10 = 0.

These parameters are set at the same time:

  • H1-xx ≠ 6A [Drive Enable]

  • H2-xx = 38 [Drive Enabled]

Correct the parameter settings.

These parameters are set at the same time:

  • H6-01 ≠ 3 [PG Speed Feedback (V/F Control)]

  • H1-xx = 7E [Reverse Rotation Identifier]

Correct the parameter settings.

These parameters are set at the same time:

  • H1-xx = 75/76 [Up 2 /Down 2 Command]

  • H3-01, H3-09 = 1 [Terminal A1, A2 Signal Level Select = 0 to +10V(Without Limit)]

Remove one of the function settings.