Code

Name

Causes

Possible Solutions

EF3

External Fault (Terminal S3)

MFDI terminal S3 caused an external fault through an external device.

  1. Find the device that caused the external fault and remove the cause.

  2. Clear the external fault input in the MFDI.

The wiring is incorrect.

Correctly connect the signal line to MFDI terminal S3.

External Fault [H1-03 = 20 to 2B] is set to MFDI terminal S3, but the terminal is not in use.

Correctly set the MFDI.

Note:

Do a Fault Reset to clear the fault.