Er-05
|
No-Load Current Error
|
The Auto-Tuning results were not in the applicable parameter setting range.
|
|
|
Auto-Tuning did not complete in a pre-set length of time.
|
|
The motor nameplate data entered during Auto-Tuning is incorrect.
|
|
|
Rotational Auto-Tuning was done with a load that was more than 30% of the rating connected to the motor.
|
-
Disconnect the machine from the motor and do Rotational Auto-Tuning again.
-
If you cannot uncouple the motor and load, make sure that the load is less than 30% of the motor rating. If a mechanical brake is installed in the motor, release the brake during Rotational Auto-Tuning.
|