UL3
|
Undertorque Detection 1
|
A fault occurred on the machine.
Example: There is a broken pulley belt.
|
Examine the machine and remove the cause of the fault
|
|
The parameters are incorrect for the load.
|
Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque Detection Time 1].
|
Note:
-
The drive detects this error if the drive output current is less than the level set in L6-02 for longer than L6-03.
-
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
-
Set the conditions that trigger the minor fault using L6-01 [Torque Detection Selection 1].
|