STPo
|
Motor Step-Out Detected
|
The motor code is set incorrectly for PM Control Methods.
|
-
Set E5-01 [PM Motor Code Selection] correctly as specified by the motor.
-
For specialized motors, refer to the motor test report and set E5-xx correctly.
|
|
The load is too large.
|
-
Increase the value set in n8-55 [Motor to Load Inertia Ratio].
-
Increase the value set in n8-51 [Pull-in Current @ Acceleration]. If the drive detects STPo during deceleration when increasing the value set in n8-51, set the value of n8-79 [Pull-in Current @ Deceleration] lower than n8-51.
-
Decrease the load.
-
Replace the drive and motor with larger capacity models.
|
|
The load inertia is too large.
|
Increase the value set in n8-55.
|
|
The acceleration/deceleration times are too short.
|
|
|
Speed response is too slow.
|
Increase the value set in n8-55.
|
Note:
Do a Fault Reset to clear the fault.
|