SToF
|
Safe Torque OFF Hardware
|
One of the two terminals H1-HC and H2-HC received the Safe Disable input signal.
|
-
Make sure that the Safe Disable signal is input from an external source to terminals H1-HC or H2-HC.
-
When the Safe Disable function is not in use, use a jumper to connect terminals H1-HC and H2-HC.
|
|
The Safe Disable input signal is wired incorrectly.
|
|
There is internal damage to one Safe Disable channel.
|
Replace the board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
|