YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E4-01
(0321)
Motor 2 Rated Current
Sets the motor rated current for motor 2 in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive rated current)
Details
E4-02
(0322)
Motor 2 Rated Slip
Sets the motor rated slip for motor 2.
(0.000 - 20.000 Hz)
E4-03
(0323)
Motor 2 Rated No-Load Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load voltage.
(0 to E4-01)
E4-04
(0324)
Motor 2 Motor Poles
Sets the number of poles for motor 2.
4
(2 - 120)
E4-05
(0325)
Motor 2 Line-to-Line Resistance
Sets the line-to-line resistance for the motor 2 stator windings.
(0.000 - 65.000 Ω)
E4-06
(0326)
Motor 2 Leakage Inductance
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage when motor 2 operates at the rated frequency and rated current.
(0.0 - 60.0%)
E4-07
(0343)
Motor 2 Saturation Coefficient 1
Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux.
0.50
(0.00 - 0.50)
E4-08
(0344)
Motor 2 Saturation Coefficient 2
Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux.
0.75
(E4-07 - 0.75)
E4-09
(033F)
Expert
Motor 2 Mechanical Loss
Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [Motor 2 Rated Power]. Usually it is not necessary to change this setting.
0.0%
(0.0 - 10.0%)
E4-10
(0340)
Motor 2 Iron Loss
Sets the motor iron loss for motor 2.
(0 - 65535 W)
E4-11
(0327)
Motor 2 Rated Power
Sets the motor rated power in the units from o1-58 [Motor Power Unit Selection].
(0.00 - 650.00 kW)