Code

Name

Causes

Possible Solutions

FbH

Excessive PID Feedback

The FbH detection level is set incorrectly.

Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID High Feedback Detection Time].

There is a problem with the PID feedback wiring.

Correct errors with the PID control wiring.

The feedback sensor is not operating correctly.

Examine the sensors on the control device side.

A fault occurred in the feedback input circuit of the drive.

Replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.

Note:
  • The drive detects this fault if the PID feedback input is more than the level set in b5-36 for longer than b5-37.

  • Do a Fault Reset to clear the fault.

  • If the drive detects this fault, it will operate the motor as specified by the stop method set in b5-12 [Feedback Loss Detection Select].