No. (Hex.) Name Description Default (Range) Ref. H3-01 (0410) Terminal A1 Signal Level Select Sets the input signal level for MFAI terminal A1. 0 0 to 10V (Lower Limit at 0) 1 0 V to 10 V (Without Lower Limit) 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. H3-02 (0434) Terminal A1 Function Selection Sets the function for MFAI terminal A1. 0 (0 - 32) Details No. (Hex.) Name Description Default (Range) Ref. H3-03 (0411) RUN Terminal A1 Gain Setting Sets the gain of the analog signal input to MFAI terminal A1. 100.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H3-04 (0412) RUN Terminal A1 Bias Setting Sets the bias of the analog signal input to MFAI terminal A1. 0.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H3-09 (0417) Terminal A2 Signal Level Select Sets the input signal level for MFAI terminal A2. 0 0-10V (LowLim=0) 1 0-10V (Without Lower Limit) 2 4 to 20 mA 3 0 to 20 mA 2 (0 - 3) Details No. (Hex.) Name Description Default (Range) Ref. H3-10 (0418) Terminal A2 Function Selection Sets the function for MFAI terminal A2. 0 (0 - 32) Details No. (Hex.) Name Description Default (Range) Ref. H3-11 (0419) RUN Terminal A2 Gain Setting Sets the gain of the analog signal input to MFAI terminal A2. 100.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H3-12 (041A) RUN Terminal A2 Bias Setting Sets the bias of the analog signal input to MFAI terminal A2. 0.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H3-13 (041B) Analog Input FilterTime Constant Sets the time constant for primary delay filters on MFAI terminals. 0.03 s (0.00 - 2.00 s) Details No. (Hex.) Name Description Default (Range) Ref. H3-14 (041C) Analog Input Terminal Enable Sel Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is ON. 1 Terminal A1 only 2 Terminal A2 only 7 Terminals A1 and A2 7 (1, 2, 7) Details No. (Hex.) Name Description Default (Range) Ref. H3-16 (02F0) Terminal A1 Offset Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this setting. 0 (-500 - +500) Details No. (Hex.) Name Description Default (Range) Ref. H3-17 (02F1) Terminal A2 Offset Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this setting. 0 (-500 - +500) Details No. (Hex.) Name Description Default (Range) Ref. H3-40 (0B5C) Mbus Reg 15C1h Input Function Sets the MEMOBUS AI1 function. F (4 - 2F) Details No. (Hex.) Name Description Default (Range) Ref. H3-41 (0B5F) Mbus Reg 15C2h Input Function Sets the MEMOBUS AI2 function. F (4 - 2F) Details No. (Hex.) Name Description Default (Range) Ref. H3-42 (0B62) Mbus Reg 15C3h Input Function Sets the MEMOBUS AI3 function. F (4 - 2F) Details No. (Hex.) Name Description Default (Range) Ref. H3-43 (117F) Mbus Reg Inputs FilterTime Const Sets the time constant to apply a primary delay filter to the MEMOBUS analog input register values. 0.00 s (0.00 - 2.00 s) Details