oPE02
|
Parameter Range Setting Error
|
Parameter settings are not in the applicable setting range.
|
-
Push to show U1-18 [oPE Fault Parameter], and find parameters that are not in the applicable setting range.
-
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx errors have priority over oPE02.
|
|
Set E2-01 ≤ E2-03 [Motor Rated Current (FLA) ≤ Motor No-Load Current].
|
Make sure that E2-01 > E2-03.
Note:
If it is necessary to set E2-01 < E2-03, first lower the value set in E2-03, and then set E2-01.
|