Code

Name

Causes

Possible Solutions

oPE02

Parameter Range Setting Error

Parameter settings are not in the applicable setting range.

  1. Push [ENTER Key] to show U1-18 [oPE Fault Parameter], and find parameters that are not in the applicable setting range.

  2. Correct the parameter settings.

    Note:

    If more than one error occurs at the same time, other oPExx errors have priority over oPE02.

Set E2-01 ≤ E2-03 [Motor Rated Current (FLA) ≤ Motor No-Load Current].

Make sure that E2-01 > E2-03.

Note:

If it is necessary to set E2-01 < E2-03, first lower the value set in E2-03, and then set E2-01.