oPE05
|
Run Cmd/Freq Ref Source Sel Err
|
The setting to assign the Run command or frequency reference to an option card or the pulse train input is incorrect.
|
Correct the parameter settings.
|
|
b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] is set, but there is no option card connected to the drive.
|
Connect an option card to the drive.
|
|
b1-02 = 3 [Run Command Selection 1 = Option PCB] is set, but there is no option card connected to the drive.
|
|
These parameters are set at the same time:
|
Set H6-01 = 0.
|