Code

Name

Causes

Possible Solutions

oPE07

Analog Input Selection Error

The settings for H3-02 and H3-10 [MFAI Function Select] and H7-30 [Virtual Analog Input Selection] overlap.

Set H3-02, H3-10, and H7-30 correctly to prevent overlap.

Note:

It is possible to set these functions to multiple analog input terminals at the same time:

  • Setting value 0 [Frequency Reference]

  • Setting values F and 1F [Not Used]

These parameters are set at the same time:

  • H3-02, H3-10, H7-30 = B [PID Feedback]

  • H6-01 = 1 [Terminal RP Pulse Train Function = PID Feedback Value]

Remove the function settings that are not in use.

These parameters are set at the same time:

  • H3-02, H3-10, H7-30 = C [PID Setpoint]

  • H6-01 = 2 [PID Setpoint Value]

These parameters are set at the same time:

  • H3-02, H3-10, H7-30 = C

  • b5-18 = 1 [PID Setpoint Selection = Enabled]

These parameters are set at the same time:

  • H6-01 = 2

  • b5-18 = 1