Causes

Possible Solutions

The drive is not in Drive Mode.

  1. Make sure that the READY LED on the keypad is ON.

  2. If the READY LED is OFF, push and hold the ESC Key to go back to the frequency reference screen (the initial screen).

The drive stopped and you pushed [LO/RE] to transfer the Run command source to the keypad.

Do one of these two:

  • Push [LO/RE].

  • Re-energize the drive.

Note:

When [LO/RE] must not change the Run command source, set o2-01 = 0 [LO/RE Key Function Selection = Disabled].

Auto-Tuning completed.

Push and hold the ESC Key to go back to the frequency reference screen (the initial screen).

Note:

When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not accept a Run command unless the drive is in Drive Mode.

The drive received a Fast Stop command.

Turn off the fast stop input signal.

The settings for the source that supplies the Run command are incorrect.

Set b1-02 [Run Command Selection 1] correctly.

The frequency reference source is not set correctly.

Set b1-01 [Frequency Reference Selection 1] correctly.

There is defective wiring in the control circuit terminals.

  • Correctly wire the drive control circuit terminals.

  • View U1-10 [Input Terminal Status] for input terminal status.

The settings for voltage input and current input of the master frequency reference are incorrect.

Examine these analog input terminal signal level settings:

  • Terminal A1: H3-01 [Terminal A1 Signal Level Select]

  • Terminal A2: DIP switch S1 and H3-09 [Terminal A2 Signal Level Select]

The selection for the sinking/sourcing mode and the internal/external power supply is incorrect.

  • For sinking mode, close the circuit between terminals SC-SP with a wire jumper.

  • For sourcing mode, close the circuit between terminals SC-SN with a wire jumper.

  • For external power supply, remove the wire jumper.

The frequency reference is too low.

  • View U1-01 [Freq Reference].

  • Increase the frequency reference to a value higher than E1-09 [Minimum Output Frequency].

The MFAI setting is incorrect.

  • Make sure that the functions set to the MFAI are correct. The frequency reference is 0 when H3-02, H3-10 = 1 [MFAI Function Select = Frequency Gain] and voltage (current) is not input.

  • Use U1-13, U1-14 [Terminal A1, A2 Input Voltage] to make sure that the analog input values set to terminals A1 and A2 are applicable.

You pushed [STOP].

Turn the Run command OFF then ON from an external input.

Note:

When you push [STOP] during operation, the drive will ramp to stop. Set o2-02 = 0 [STOP Key Function Selection = Disabled] to disable the [STOP] function.

The 2-wire sequence and 3-wire sequence are not set correctly.

  • Set one of the parameters H1-03 to H1-07 [Terminals S3 to S7 Function Select] to 0 [3-Wire Sequence] to enable the 3-wire sequence.

  • If a 2-wire sequence is necessary, make sure that H1-03 to H1-07 ≠ 0.