The drive and motor system are at the torque limit or current suppression will not let the drive accelerate.
|
-
Decrease the load.
-
Use a larger motor.
Note:
Although the drive has a Stall Prevention function and a Torque Compensation Limit function, if you try to accelerate too fast or try to drive a load that is too large, it can be too much for the limits of the motor.
|
|
Torque limit is set incorrectly.
|
Set the torque limit correctly.
|
|
The acceleration time setting is too short.
|
Examine the values set in C1-01, C1-03, C1-05, or C1-07 [Acceleration Time] and set them to applicable values.
|
|
The load is too large.
|
-
Increase the acceleration time.
-
Examine the mechanical brake and make sure that it is fully releasing.
-
Decrease the load to make sure that the output current stays less than the motor rated current.
-
Use a larger motor.
Note:
-
In extruder and mixer applications, the load can increase as the temperature decreases.
-
Although the drive has a Stall Prevention function and a Torque Compensation Limit function, if you try to accelerate too fast or try to drive a load that is too large, it can be too much for the limits of the motor.
|
|
The frequency reference is low.
|
-
Examine E1-04 [Maximum Output Frequency] and increase the setting if it is set too low.
-
Examine U1-01 [Frequency Reference] for the correct frequency reference.
-
Examine the multi-function input terminals to see if a frequency reference signal switch is set.
-
When you use an MFAI, examine the low gain level set in H3-03, H3-11 [Terminal A1, A2 Gain Setting].
|
|
The frequency reference is set incorrectly.
|
When H3-10 = 1 Terminal A2 Function Selection = Frequency Gain], see if the drive is set for voltage (current).
|
|
The motor characteristics and drive parameter settings are not compatible.
|
-
Set the correct V/f pattern to agree with the characteristics of the motor.
-
Examine the V/f pattern set in E1-03 [V/f Pattern Selection].
-
Do Rotational Auto-Tuning.
|
|
The drive is operating in vector control mode, but you did not complete Auto-Tuning.
|
|
|
The Stall Prevention level during acceleration setting is too low.
|
Increase the value set in L3-02 [Stall Prevent Level during Accel].
Note:
If the L3-02 value is too low, the acceleration time can be unsatisfactorily long.
|
|
The Stall Prevention level during run setting is too low.
|
Increase the value set in L3-06 [Stall Prevent Level during Run].
Note:
If the L3-06 value is too low, speed will decrease before the drive outputs torque.
|
|
The drive is at the limit of the V/f motor control method.
|
-
When the motor cable is longer than 50 m (164 ft), do Auto-Tuning for line-to-line resistance.
-
Set the V/f pattern to “High Starting Torque”.
-
Use a Vector Control method.
Note:
V/f control method does not supply high torque at low speeds.
|