The stall prevention during deceleration setting is incorrect.
|
-
Examine the setting for L3-04 [Decel Stall Prevention Selection].
-
When the drive has a dynamic braking option installed, set L3-04 = 0 [Disabled].
-
If the drive detects ov [Overvoltage], set L3-04 = 3 [General Purpose w/ DB resistor].
|
|
The deceleration time setting is too long.
|
Set C1-02, C1-04, C1-06, or C1-08 [Deceleration Times] to applicable values.
|
|
The motor torque is not sufficient.
|
Use a larger motor.
Note:
If these items are correct, the demand on the motor is more than the motor capacity:
|
|
The drive and motor system reached the torque limit.
|
-
Examine the values set in L7-01 to L7-04 [Torque Limit] and increase them if necessary.
Note:
If the torque limit is enabled, deceleration time can increase because the drive cannot output more torque than the limit.
-
If H3-02, H3-10 = 10, 11, 12, 15 [MFAI Function Select = Torque Limit], examine the settings for the MFAIs.
-
Examine the values set in H3-02 and H3-10.
-
Use U1-13, U1-14 [Terminal A1, A2 Input Voltage] to make sure that the analog input values set to terminals A1 and A2 are applicable.
|
|
The load is more than the internal torque limit as specified by the drive rated current.
|
Replace the drive with a larger capacity model.
|