CE
|
Modbus Communication Error
|
The communications cable wiring is incorrect.
|
Correct wiring errors.
|
|
There is a short circuit in the communications cable or the communications cable is not connected.
|
|
|
Electrical interference caused a communication data error.
|
-
Examine the control circuit lines, main circuit lines, and ground wiring, and decrease the effects of electrical interference.
-
Make sure that a magnetic contactor is not the source of the electrical interference, then use a Surge Protective Device if necessary.
-
Use only the recommended cables or other shielded line. Ground the shield on the controller side or the drive input power side.
-
Separate the communication wiring from drive power lines, and install a noise filter to the input side of the power supply for communication.
-
Decrease the effects of electrical interference from the controller.
|
|
The communication protocol is not compatible.
|
|
|
The value set in H5-09 [CE Detection Time] is too small for the communications cycle.
|
|
|
The controller software or hardware is causing a communication problem.
|
Examine the controller and remove the cause of the problem.
|
Note:
-
The drive detects this error if it does not correctly receive control data for the CE detection time set to H5-09.
-
If the drive detects this error, the terminal assigned to H2-01 to H2-04 = 10 [MFDO Function Select = Alarm] will activate.
-
If the drive detects this error, it will operate the motor as specified by the stopping method set in H5-04 [Communication Error Stop Method].
|