UL3
|
Undertorque Detection 1
|
A fault occurred on the machine.
Example: There is a broken pulley belt.
|
Examine the machine and remove the cause of the fault.
|
|
The parameters are incorrect for the load.
|
Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque Detection Time 1] settings.
|
Note:
-
The drive detects this error if the drive output current is less than the level set in L6-02 for longer than L6-03.
-
Do a Fault Reset to clear the fault.
-
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-01 [Torque Detection Selection 1].
|