The drive is not in Drive Mode.
|
-
Make sure that the keypad shows [Rdy].
-
If the keypad does not show [Rdy], go back to the Home screen.
|
|
The drive stopped, was pushed, and changed the Run command source to the keypad.
|
Do one of these two:
-
Push .
-
Re-energize the drive.
Note:
Set o2-01 = 0 [LO/RE Key Function Selection = Disabled] to prevent changing the Run command source with .
|
|
Auto-Tuning completed.
|
Go back to the Home screen on the keypad.
Note:
When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not accept a Run command unless the drive is in Drive Mode.
|
|
The drive received a fast stop command.
|
Turn off the fast stop input signal.
|
|
The settings for the source that supplies the Run command are incorrect.
|
Set b1-02 [Run Command Selection 1] correctly.
|
|
The frequency reference source is set incorrectly.
|
Set b1-01 [Frequency Reference Selection 1] correctly.
|
|
There is defective wiring in the control circuit terminals.
|
|
|
The settings for voltage input and current input of the master frequency reference are incorrect.
|
Examine these analog input terminal signal level settings:
-
Terminal A1: DIP switch S1-1 and H3-01 [Terminal A1 Signal Level Select]
-
Terminal A2: DIP switch S1-2 and H3-09 [Terminal A2 Signal Level Select]
-
Terminal A3: DIP switch S4, S1-3 and H3-05 [Terminal A3 Signal Level Select]
|
|
The selection for the sinking/sourcing mode and the internal/external power supply is incorrect.
|
-
For sinking mode, close the circuit between terminals SC-SP with a wire jumper.
-
For sourcing mode, close the circuit between terminals SC-SN with a wire jumper.
-
For external power supply, remove the wire jumper.
|
|
The frequency reference is too low.
|
|
|
The MFAI setting is incorrect.
|
-
Make sure that the functions set to the MFAI are correct. The frequency reference is 0 when H3-02, H3-10, H3-06 = 1 [MFAI Function Select = Frequency Gain] and voltage (current) is not input.
-
View U1-13 to U1-15 [Terminal A1, A2, A3 Input Voltage] to see if the analog input values set to terminals A1, A2, and A3 are applicable.
|
|
was pushed.
|
Turn the Run command OFF then ON from an external input.
Note:
When you push during operation, the drive will ramp to stop. Set o2-02 = 0 [STOP Key Function Selection = Disabled] to disable the function.
|
|
The 2-wire sequence and 3-wire sequence are set incorrectly.
|
-
Set one of the parameters H1-03 to H1-08 [Terminals S3 to S8 Function Select] to 0 [3-Wire Sequence] to enable the 3-wire sequence.
-
If a 2-wire sequence is necessary, make sure that H1-03 to H1-08 ≠ 0.
|