STo
|
Safe Torque OFF
|
Safe Disable inputs H1-HC and H2-HC are open.
|
-
Make sure that the Safe Disable signal is input from an external source to terminal H1-HC and H2-HC.
-
When the Safe Disable function is not in use, use a jumper to connect terminals H1-HC and H2-HC.
|
|
There is internal damage to the two Safe Disable channels.
|
Replace the board or the drive. Contact Yaskawa or your nearest sales representative to replace the board.
|
Note:
-
The drive will not output an alarm signal for this alarm.
-
If the drive detects this error, the terminal set to H2-01 to H2-04 = 21 [MFDO Function Select = Safe Torque OFF] will activate.
|