UL4
|
Undertorque Detection 2
|
A fault occurred on the machine.
Example: There is a broken pulley belt.
|
Examine the machine and remove the cause of the fault.
|
|
The parameters are incorrect for the load.
|
Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque Detection Time 2] settings.
|
Note:
-
The drive detects this error if the drive output current is less than the level set in L6-05 for longer than L6-06.
-
If detected, the terminal assigned to H2-01 to H2-04 = 10 [MFDO Function Select = Alarm] will be ON.
-
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-04 [Torque Detection Selection 2].
|