oPE03
|
Multi-Function Input Setting Err
|
The settings for these parameters do not agree:
-
F3-10 to F3-25 [Terminal D1 to DF Function Selection]
-
H1-01 to H1-08 [Terminals S1 to S8 Function Selection]
-
H7-01 to H7-04 [Virtual Multi-Function Inputs 1 to 4]
|
Correct the parameter settings.
|
|
The settings for the standby mode function do not agree:
|
Correct the parameter settings.
|
|
The settings for MFDIs overlap.
Note:
This does not include H1-xx = 20 to 2F [MFDI Function Select = External Fault] and [Reserved].
|
Set the parameters correctly to prevent MFDI function overlap.
|
|
These pairs of MFDI functions are not set to Digital Inputs (H1-xx, F3-10 to F3-25, and H7-01 to H7-04) at the same time:
-
Setting values 10 [Up Command] and 11 [Down Command]
-
Setting values 75 [Up 2 Command] and 76 [Down 2 Command]
-
Setting values 42 [Run Command (2-Wire Sequence 2)] and 43 [FWD/REV (2-Wire Sequence 2)]
|
Set the MFDI pairs.
|
|
A minimum of two of these MFDI combinations are set to Digital Inputs (H1-xx, F3-10 to F3-25, and H7-01 to H7-04) at the same time:
-
Setting values 10 [Up Command] and 11 [Down Command]
-
Setting values 75 [Up 2 Command] and 76 [Down 2 Command]
-
Setting value A [Accel/Decel Ramp Hold]
-
Setting value 1E [Reference Sample Hold]
-
Setting values 44 to 46 [Add Offset Frequency 1 to 3 (d7-01 to d7-03)]
|
Remove the function settings that are not in use.
|
|
The parameter settings are enabled at the same time.
|
|
|
These commands are set in Digital Inputs (H1-xx, F3-10 to F3-25, and H7-01 to H7-04) at the same time:
-
Setting values 61 [Speed Search from Fmax] and 62 [Speed Search from Fref]
-
Setting values 65, 66, 7A, 7B [KEB Ride-Thru 1 or 2 Activate] and 68 [High Slip Braking (HSB) Activate]
-
Setting values 16 [Motor 2 Selection] and 1A [Accel/Decel Time Selection 2]
-
Setting values 65, 66 [KEB Ride-Thru 1 Activate] and 7A, 7B [KEB Ride-Thru 2 Activate]
-
Setting values 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-Wire)] and 42, 43 [Run Command (2-Wire Sequence 2), FWD/REV (2-Wire Sequence 2)]
-
Setting values 60 [DC Injection Braking Command] and 6A [Drive Enable]
-
Setting values 16 [Motor 2 Selection] and 75, 76 [Up 2 Command, Down 2 Command]
|
Remove the function settings that are not in use.
|
|
Settings for N.C. and N.O. input [H1-xx] for these functions were selected at the same time:
|
Remove one of the function settings.
|
|
These settings were entered while H1-xx = 2 [External Reference 1/2 Selection]:
|
Set H6-01 = 0.
|
|
These settings were entered while H1-xx = 2 [External Reference 1/2 Selection]:
|
Connect an input option card to the drive.
|
|
These settings were entered while H1-xx = 2 [External Reference 1/2 Selection]:
|
Set H3-02 = 0 or H3-10 = 0.
|
|
These parameters are set at the same time:
|
Correct the parameter settings.
|
|
These parameters are set at the same time:
|
Correct the parameter settings.
|
|
These parameters are set at the same time:
-
H1-xx = 75/76 [Up 2 /Down 2 Command]
-
H3-01, H3-05, H3-09 = 1 [Terminal A1, A2, A3 Signal Level Select = -10 to +10V (Bipolar Reference)]
|
Remove one of the function settings.
|
|
These parameters are set at the same time:
|
Remove one of the function settings.
|
|
These settings do not agree:
|
Correct the parameter settings.
Note:
The Motor Switch function is not available with the PG-RT3 option.
|