oL7
|
High Slip Braking Overload
|
The load inertia is too large.
|
-
Decrease deceleration times in C1-02, C1-04, C1-06, and C1-08 [Deceleration Times] for applications that do not use High Slip Braking.
-
Use a braking resistor to decrease the deceleration time.
|
|
An external force on the load side rotated the motor.
|
|
Something is preventing deceleration on the load side.
|
|
The value set in n3-04 [HSB Overload Time] is too small.
|
-
Increase the value set in n3-04.
-