Er-12
|
Current Detection Error
|
There is a phase loss in the drive input power. (U/T1, V/T2, W/T3)
|
Examine and repair motor wiring.
|
|
The current exceeded the current rating of the drive.
|
-
Check the motor wiring for any short circuits between the wires.
-
Check and turn ON any magnetic contactors used between motors.
-
Replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|
|
The output current is too low.
|
|
You tried Auto-Tuning without a motor connected to the drive.
|
Connect the motor and do Auto-Tuning.
|
|
There was a current detection signal error.
|
Replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|