|
oPE08
|
Parameter Selection Error
|
You set a function that is not compatible with the control method set in A1-02 [Control Method Selection].
|
-
Push to show U1-18 [oPE Fault Parameter], and find parameters that are not in the applicable setting range.
-
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx errors have priority over oPE02.
|
|
When A1-02 = 2 [Control Method Selection = OLV], you used these parameter settings:
|
-
Set n2-02 < n2-03.
-
Set C4-02 < C4-06.
|
|
When A1-02 = 0 [Control Method Selection = V/f], you used these parameter settings:
|
Correct the parameter settings.
Note:
You cannot use Speed Feedback (V/F Control) with the Motor Switch function.
|
|
When A1-02 = 5 [PM Open Loop Vector], you set E5-02 to E5-07 [PM Motor Parameters] = 0.
|
-
Set E5-01 [PM Motor Code Selection] correctly as specified by the motor.
-
For specialized motors, refer to the motor test report and set E5-xx correctly.
|
|
When A1-02 = 5 to 7 [Control Methods for PM Motors], you used these parameter settings:
|
Set E5-09 or E5-24 to the correct value.
|
|
When A1-02 = 5 to 7, you set E5-09 ≠ 0 and E5-24 ≠ 0.
|
Set E5-09 = 0 or E5-24 = 0.
|
|
When A1-02 = 6 [PM Advanced Open Loop Vector], you used these parameter settings:
|
Correct the parameter settings.
|
|
When A1-02 = 6, you set these parameters:
|
Correct the parameter settings.
|
|
When A1-02 = 8 [EZOLV], you used these parameter settings:
-
E9-01 = 1, 2 [Motor Type Selection = Permanent Magnet (PM), Synchronous Reluctance (SynRM)]
-
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
|
When E9-01 = 1 or 2, set b3-24 = 1 [Speed Estimation].
|