oPE09
|
PID Control Selection Fault
|
These parameters are set at the same time:
-
b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz]
-
b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer]
|
|
|
These parameters are set at the same time:
-
b5-01 = 1, 2 [Enabled (Standard), Enabled (D = Feedforward)]
-
d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠ 0.0%]
-
b5-11 = 1 [PID Output Reverse Selection = Negative Output Accepted]
|
Correct the parameter settings.
|
|
These parameters are set at the same time:
-
b5-01 = 3, 4 [Trim (Fref+PID Out, D = Fdbk), Trim (Fref+PID Out, D = FeedFwd)]
-
d2 -02≠ 0.0 has been set.
|
Correct the parameter settings.
|
Note:
The drive detects this error if the PID control function selection is incorrect.
(When b5-01 = 1 to 4 [PID Mode Setting = PID Control Enabled])
|