LF
|
Output Phase Loss
|
The motor main circuit cable is disconnected.
|
Connect motor main circuit cable wiring. Correct wiring errors in the main circuit drive input power.
|
|
There is a disconnection in the motor coil winding.
|
If a coil is disconnected, measure the motor Line-to-Line Resistance and replace the motor.
|
|
The screws on the drive output terminals are loose.
|
Tighten the terminal screws to the correct tightening torque.
|
|
The rated output current of the motor is less than 5% of the drive rated current.
|
Examine the drive capacity or the motor output to be applied.
|
|
You are trying to use a single-phase motor.
|
The drive cannot operate a single-phase motor.
|
|
The output transistor in the drive is damaged.
|
|
Note:
-
The drive detects this fault if phase loss occurs on the output side of the drive.
-
Do a Fault Reset to clear the fault.
-
Set L8-07 [Output Phase Loss Protection Sel] to enable and disable LF detection.
|