Code

Name

Causes

Possible Solutions

oPE33

Digital Output Selection Error

These two parameters are set at the same time:

  • H2-60 ≠ F [Term M1-M2 Secondary Function ≠ Not Used]

  • H2-01 = 1xx [Term M1-M2 Function Selection = Inverse output of xx]

Clear the H2-01 to H2-04 = 1xx settings.

Note:

It is not possible to set H2-01 to H2-04 = 1xx when using output functions for logic operations (H2-60, H2-63, H2-66, H2-69 ≠ F).

These two parameters are set at the same time:

  • H2-63 ≠ F [Term M3-M4 Secondary Function ≠ Not Used]

  • H2-02 = 1xx [Term M3-M4 Function Selection = Inverse output of xx]

These two parameters are set at the same time:

  • H2-66 ≠ F [Term P1-C1 Secondary Function ≠ Not Used]

  • H2-03 = 1xx [Term P1-C1 Function Selection = Inverse output of xx]

These two parameters are set at the same time:

  • H2-69 ≠ F [Digital Output4 Secondary Func ≠ Not Used]

  • H2-04 = 1xx [Term P2-C2 Function Selection = Inverse output of xx]

These parameter pairs are set incorrectly:

  • H2-21 [Comparator 1 Lower Limit] > H2-22 [Comparator 1 Upper Limit]

  • H2-27 [Comparator 2 Lower Limit] > H2-28 [Comparator 2 Upper Limit]

  • Set parameters H2-21H2-22.

  • Set parameters H2-27H2-28.