SC
|
Short Circuit/IGBT Failure
|
Overheating caused damage to the motor or the motor insulation is not satisfactory.
|
Measure the motor insulation resistance, and replace the motor if there is electrical conduction or unserviceable insulation.
|
|
The motor main circuit cable is contacting ground to make a short circuit.
|
-
Examine the motor main circuit cable for damage, and repair short circuits.
-
Measure the resistance between the motor main circuit cable and the ground terminal. If there is electrical conduction, replace the cable.
|
|
A short circuit or ground fault on the drive output side caused damage to the output transistor of the drive.
|
-
Make sure that there is not a short circuit in terminal B1 and terminals U/T1, V/T2, and W/T3. Make sure that there is not a short circuit in terminals - and terminals U/T1, V/T2, and W/T3.
-
If there is a short circuit, contact Yaskawa or your nearest sales representative.
|
|
When A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, or CLV/PM], the output current is more than the value set in L8-27 [Overcurrent Detection Gain].
|
Set L8-27 correctly.
|
Note:
-
The drive detects this error if there is a short circuit or ground fault on the drive output side, or an IGBT failure.
-
Do a Fault Reset to clear the fault.
|