Code

Name

Causes

Possible Solutions

oPE15

Torque Control Setting Error

More than one parameter is selecting torque control at the same time.

  • d5-01 = 1 [Torque Control Selection = Torque Control]

  • H1-xx = 71 [MFDI Function Select = Torque Control]

Correct the parameter settings.

Droop control and Feed Forward control are enabled at the same time that torque control is selected.

  • d5-01 = 1 or H1-xx = 71

  • b7-01 ≠ 0.0 [Droop Control Gain ≠ 0.0%] or n5-01 = 1 [Feed Forward Control Selection = Enabled]

Correct the parameter settings.

KEB Ride-Thru 2 (N.O., N.C.) is enabled at the same time that torque control is selected.

  • d5-01 = 1 or H1-xx = 71

  • H1-xx = 7A [KEB Ride-Thru 2 Activate (N.C.)] or H1-xx = 7b [KEB Ride-Thru 2 Activate (N.O.)]

Correct the parameter settings.

After a momentary power loss, drive operation will enable KEB when torque control is selected.

  • d5-01 = 1 or H1-xx = 71

  • L2-01 = 3, 4, 5 [Power Loss Ride Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU Power, or Kinetic Energy Backup: DecelStop]

Correct the parameter settings.

Optimal deceleration or overexcitation deceleration 2 is enabled at the same time that torque control is selected.

  • d5-01 = 1 or H1-xx = 71

  • L3-04 = 2, 5 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp), Overexcitation/High Flux 2]

Correct the parameter settings.