Code

Name

Causes

Possible Solutions

oFC06

Option Card Error Occurred at Option Port (CN5-C)

A fault occurred in the option.

  1. De-energize the drive.

  2. Make sure that the option is correctly connected to the connector.

  3. Re-energize the drive. If the problem continues, replace the option.

You re-energized the drive when:

  • There is an encoder option installed the drive

  • žThe drive main circuit power supply is energized

  • There is an external 24 V power supply connected to terminals PS-AC.

  1. De-energize the drive main circuit power supply and the external 24 V power supply to terminals PS-AC.

  2. After the keypad display goes out, energize the drive main circuit power supply again.

  3. Supply the external 24 V power to terminals PS-AC.

When you use an encoder, de-energize the drive main circuit power supply.

Note:

Do a Fault Reset to clear the fault.