oH3
|
Motor Overheat (PTC Input)
|
The thermistor wiring that detects motor temperature is defective.
|
Correct wiring errors.
|
|
A fault occurred on the machine.
Example: The machine is locked.
|
Examine the machine and remove the cause of the fault
|
|
The motor has overheated.
|
-
Check the load level, acceleration/deceleration time, and motor start/stop frequency (cycle time).
-
Decrease the load.
-
Increase the values set in C1-01 to C1-08 [Acceleration/Deceleration Times].
-
Set E2-01 [Motor Rated Current (FLA)] correctly to the value specified by the motor nameplate.
-
Make sure that the motor cooling system is operating correctly, and repair or replace it if it is damaged.
-
Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2, adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload tolerance will decrease at low speeds.
|
Note:
-
When H3-02, H3-10, or H3-06 = E [MFAI Function Selection = Motor Temperature (PTC Input)], the drive detects this fault if the motor overheat signal entered to an analog input terminal A1, A2, or A3 is more than the alarm detection level.
-
If the drive detects this error, the terminal set to H2-01 to H2-04 = 10 [MFDO Function Select = Alarm] will activate.
-
If the drive detects this error, it will operate the motor as specified by the stopping method set in L1-03 [Motor Thermistor oH Alarm Select].
|