Code

Name

Causes

Possible Solutions

dEv

Speed Deviation

The load is too heavy.

Decrease the load.

Acceleration and deceleration times are set too short.

Increase the values set in C1-01 to C1-08 [Acceleration/Deceleration Time].

The dEv detection level settings are incorrect.

Adjust F1-10 [Speed Deviation Detection Level] and F1-11 [Speed Deviation Detect DelayTime].

The load is locked up.

Examine the machine.

The holding brake is stopping the motor.

Release the holding brake.

Note:
  • The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of F1-10 for longer than F1-11.

  • Do a Fault Reset to clear the fault.

  • If the drive detects this error, the drive will operate the motor as specified by the stopping method set in F1-04 [Speed Deviation Detection Select].