CoF
|
Current Offset Fault
|
The drive starts operation while the induced voltage stays in the motor (during coasting to a stop or after fast deceleration).
|
-
Make a sequence that does not restart operation when induced voltage stays in the motor.
-
Set b3-01 = 1 [Speed Search at Start Selection = Enabled].
-
Use Speed Search from Fmax or Fref [H1-xx = 61, 62] to do a speed search through one of the external terminals.
Note:
When controlling the PM motor, External Speed Search commands 1 and 2 operate the same.
|
|
A drive hardware problem occurred.
|
|