No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d2-01

(0289)

Frequency Reference Upper Limit

Sets maximum limit for all frequency references. The maximum output frequency is 100%.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Motor Max Revolutions]

100.0%

(0.0 - 110.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d2-02

(028A)

Frequency Reference Lower Limit

Sets minimum limit for all frequency references. The maximum output frequency is 100%.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Motor Max Revolutions]

0.0%

(0.0 - 110.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

d2-03

(0293)

Analog Frequency Ref Lower Limit

Sets the lower limit for the master frequency reference (the first frequency of the multi-step speed reference) as a percentage. The maximum output frequency is 100%.

Note:

Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

  • A1-02 ≠ 8: E1-04 [Maximum Output Frequency]

  • A1-02 = 8: E9-02 [Maximum Speed]

0.0%

(0.0 - 110.0%)

Details