Jump to main content

Three-Phase 200 V Class

 

No. 1

Name

Unit

Default

-

Drive Model

-

2004

2006

2008

2010

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

62

63

64

65

E2-11

(E4-11)

Motor Rated Power

kW

0.4

0.75

0.75

1.1

1.1

1.5

1.5

2.2

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

1

1

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

288.2

223.7

223.7

196.6

196.6

169.4

169.4

156.8

C5-17

(C5-37)

Motor Inertia

kgm2

0.0015

0.0028

0.0028

0.0068

0.0068

0.0068

0.0068

0.0088

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

1.9

3.3

3.3

4.9

4.9

6.2

6.2

8.5

E2-02

(E4-02)

Motor Rated Slip

Hz

2.9

2.5

2.5

2.6

2.6

2.6

2.6

2.9

E2-03

(E4-03)

Motor No-Load Current

A

1.2

1.8

1.8

2.3

2.3

2.8

2.8

3

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

9.842

5.156

5.156

3.577

3.577

1.997

1.997

1.601

E2-06

(E4-06)

Motor Leakage Inductance

%

18.2

13.8

13.8

18.5

18.5

18.5

18.5

18.4

E2-10

(E4-10)

Motor Iron Loss

W

14

26

26

38

38

53

53

77

E5-01

PM Motor Code Selection

-

1202

1202

1203

1203

FFFF

FFFF

1205

1205

L2-02

Power Loss Ride Through Time

s

0.1

0.1

0.2

0.2

0.3

0.3

0.3

0.3

L2-03

Minimum Baseblock Time

s

0.2

0.3

0.3

0.4

0.4

0.4

0.4

0.5

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

L2-05

Undervoltage Detection Lvl (Uv1)

-

190

190

190

190

190

190

190

190

L3-24

Motor Accel Time @ Rated Torque

s

0.178

0.142

0.142

0.142

0.142

0.166

0.166

0.145

L8-02

Overheat Alarm Level

°C

115

115

115

115

115

115

115

115

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

1

1

1

1

1

1

1

1

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.178

0.142

0.142

0.142

0.142

0.166

0.166

0.145

 
 

No. 1

Name

Unit

Default

-

Drive Model

-

2012

2018

2021

2030

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

66

67

68

6A

E2-11

(E4-11)

Motor Rated Power

kW

2.2

3.0

3.0

3.7

3.7

5.5

5.5

7.5

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

156.8

136.4

136.4

122.9

122.9

94.75

94.75

72.69

C5-17

(C5-37)

Motor Inertia

kgm2

0.0088

0.0158

0.0158

0.0158

0.0158

0.0255

0.026

0.037

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

8.5

11.4

11.4

14

14

19.6

19.6

26.6

E2-02

(E4-02)

Motor Rated Slip

Hz

2.9

2.7

2.7

2.73

2.73

1.5

1.5

1.3

E2-03

(E4-03)

Motor No-Load Current

A

3

3.7

3.7

4.5

4.5

5.1

5.1

8

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

1.601

1.034

1.034

0.771

0.771

0.399

0.399

0.288

E2-06

(E4-06)

Motor Leakage Inductance

%

18.4

19

19

19.6

19.6

18.2

18.2

15.5

E2-10

(E4-10)

Motor Iron Loss

W

77

91

91

112

112

172

172

262

E5-01

PM Motor Code Selection

-

1206

1206

FFFF

FFFF

1208

1208

120A

120A

L2-02

Power Loss Ride Through Time

s

0.5

0.5

1

1

1

1

1

1

L2-03

Minimum Baseblock Time

s

0.5

0.5

0.5

0.6

0.6

0.7

0.7

0.8

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

L2-05

Undervoltage Detection Lvl (Uv1)

-

190

190

190

190

190

190

190

190

L3-24

Motor Accel Time @ Rated Torque

s

0.145

0.145

0.145

0.154

0.154

0.168

0.168

0.175

L8-02

Overheat Alarm Level

°C

124

124

110

110

110

110

110

110

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

1

1

1

1

1

1

1

1

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.145

0.145

0.145

0.154

0.154

0.168

0.168

0.175

 
 

No. 1

Name

Unit

Default

-

Drive Model

-

2042

2056

2070

2082

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

6B

6D

6E

6F

E2-11

(E4-11)

Motor Rated Power

kW

7.5

11

11

15

15

18.5

18.5

22

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

72.69

70.44

70.44

63.13

63.13

57.87

57.87

51.79

C5-17

(C5-37)

Motor Inertia

kgm2

0.037

0.053

0.053

0.076

0.076

0.138

0.138

0.165

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

26.6

39.7

39.7

53

53

65.8

65.8

77.2

E2-02

(E4-02)

Motor Rated Slip

Hz

1.3

1.7

1.7

1.6

1.6

1.67

1.67

1.7

E2-03

(E4-03)

Motor No-Load Current

A

8

11.2

11.2

15.2

15.2

15.7

15.7

18.5

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

0.288

0.23

0.23

0.138

0.138

0.101

0.101

0.079

E2-06

(E4-06)

Motor Leakage Inductance

%

15.5

19.5

19.5

17.2

17.2

15.7

20.1

19.5

E2-10

(E4-10)

Motor Iron Loss

W

262

245

245

272

272

505

505

538

E5-01

PM Motor Code Selection

-

120B

120B

120D

120D

120E

120E

120F

120F

L2-02

Power Loss Ride Through Time

s

1

1

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

0.8

0.9

0.9

1

1

1

1

1

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.3

0.3

0.6

0.6

0.6

0.6

0.6

L2-05

Undervoltage Detection Lvl (Uv1)

-

190

190

190

190

190

190

190

190

L3-24

Motor Accel Time @ Rated Torque

s

0.175

0.265

0.265

0.244

0.244

0.317

0.317

0.355

L8-02

Overheat Alarm Level

°C

110

110

115

115

120

120

133

130

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

1

1

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.175

0.265

0.265

0.244

0.244

0.317

0.317

0.355

 

No. 1

Name

Unit

Default

-

Drive Model

-

2110

2138

2169

2211

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

70

72

73

74

E2-11

(E4-11)

Motor Rated Power

kW

22

30

30

37

37

45

45

55

b3-04

V/f Gain during Speed Search

%

100

80

80

80

80

80

80

80

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

2.00

b8-04

Energy Saving Coefficient Value

-

51.79

46.27

46.27

38.16

38.16

35.78

35.78

31.35

C5-17

(C5-37)

Motor Inertia

kgm2

0.165

0.220

0.220

0.273

0.273

0.333

0.333

0.490

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

77.2

105

105

131

131

160

160

190

E2-02

(E4-02)

Motor Rated Slip

Hz

1.7

1.8

1.8

1.33

1.33

1.6

1.6

1.43

E2-03

(E4-03)

Motor No-Load Current

A

18.5

21.9

21.9

38.2

38.2

44

44

45.6

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

0.079

0.064

0.064

0.039

0.039

0.03

0.03

0.022

E2-06

(E4-06)

Motor Leakage Inductance

%

19.5

20.8

20.8

18.8

18.8

20.2

20.2

20.5

E2-10

(E4-10)

Motor Iron Loss

W

538

699

699

823

823

852

852

960

E5-01

PM Motor Code Selection

-

1210

1210

1212

1212

1213

1213

1214

1214

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

1

1.1

1.1

1.1

1.1

1.2

1.2

1.3

L2-04

Powerloss V/f Recovery Ramp Time

s

0.6

0.6

0.6

0.6

0.6

1

1

1

L2-05

Undervoltage Detection Lvl (Uv1)

-

190

190

190

190

190

190

190

190

L3-24

Motor Accel Time @ Rated Torque

s

0.355

0.323

0.323

0.32

0.32

0.387

0.387

0.317

L8-02

Overheat Alarm Level

°C

105

105

115

115

105

105

105

105

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.355

0.323

0.323

0.32

0.32

0.387

0.387

0.317

 

No. 1

Name

Unit

Default

-

Drive Model

-

2257

2313

2360

2415

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

75

76

77

78

E2-11

(E4-11)

Motor Rated Power

kW

55

75

75

90

90

110

110

110

b3-04

V/f Gain during Speed Search

%

80

80

80

80

80

80

80

80

b3-06

Speed Estimation Current Level 1

-

0.5

0.7

0.7

0.7

0.7

0.7

0.7

0.7

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

31.35

23.1

23.1

20.65

20.65

18.12

18.12

18.12

C5-17

(C5-37)

Motor Inertia

kgm2

0.49

0.90

0.90

1.10

1.10

1.90

1.90

1.90

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

190

260

260

260

260

260

260

260

E2-02

(E4-02)

Motor Rated Slip

Hz

1.43

1.39

1.39

1.39

1.39

1.39

1.39

1.39

E2-03

(E4-03)

Motor No-Load Current

A

45.6

72

72

72

72

72

72

72

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

0.022

0.023

0.023

0.023

0.023

0.023

0.023

0.023

E2-06

(E4-06)

Motor Leakage Inductance

%

20.5

20

20

20

20

20

20

20

E2-10

(E4-10)

Motor Iron Loss

W

960

1200

1200

1200

1200

1200

1200

1200

E5-01

PM Motor Code Selection

-

1215

1215

1216

1216

FFFF

FFFF

FFFF

FFFF

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

1.3

1.5

1.5

1.5

1.5

1.7

1.7

1.7

L2-04

Powerloss V/f Recovery Ramp Time

s

1

1

1

1

1

1

1

1

L2-05

Undervoltage Detection Lvl (Uv1)

-

190

190

190

190

190

190

190

190

L3-24

Motor Accel Time @ Rated Torque

s

0.317

0.533

0.533

0.592

0.592

0.646

0.646

0.646

L8-02

Overheat Alarm Level

°C

105

105

105

105

105

105

105

105

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

100

100

100

100

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

1.00

1.00

1.00

1.00

n5-02

Motor Inertia Acceleration Time

s

0.317

0.533

0.533

0.592

0.592

0.646

0.646

0.646

1

Parameters in parentheses are for motor 2.

2

The display units are different for different models: The units are Ω for models 2004 to 2415, 4002 to 4675 and mΩ for models 4810 to 4H12.

3

The display units are different for different models: The units are Ω for models 2004 to 2415, 4002 to 4675 and mΩ for models 4810 to 4H12.